» MNL-VXXX

  • Local network control
  • Damper and fan adjustment
  • Setpoint monitoring and adjustment
  • Flow validation and calibration
  • Sequence, calibration and control system log

I/O Configuration
Universal Input: 3 Channels
Digital Outputs: 3 Channels
Chassis
Dimensions: 197mm x 159mm x 63mm
Environment
Operating Temp: 0°C to 50°C (32°F to 131°F)
Storage Temp: -40°C to 71°C (-40°F to 160°F)
Relative Humidity: 5% to 95%, non-condensing

OVERVIEW

The I/A Series MicroNet VAV (Variable Air Volume) Controllers are interoperable controllers designed in accordance with LonMark® guidelines. When programmed using WorkPlace Tech Tool or loaded with a pre-engineered application, they provide a wide range of control strategies for pressure independent terminal boxes with, or without, reheat capabilities. Both models provide an integral actuator with manual override, an integral patented pressure transducer, one digital input, one universal input, Sensor Link (S-Link) support, LED indication, and over-the-shaft damper mounting. In addition, the MNL-V2RVx model provides one analog output and three digital outputs. These controllers can function either in a standalone mode or as part of a LonWorks® FTT-10 Free Topology communications network.

The VAV series controllers offer the advantages of standalone or networked control. Using a I/A Series MicroNet Sensor (MN-Sx series), the operator can monitor controller performance and edit operational values. The WorkPlace Tech Tool software is used to program the controllers or download applications from the application library.